Control Box Installation
1. There are two rectangular tabs on the top of the control box. Align these tabs to the rectangular holes located at
the top of the bracket.
2. Insert the tabs into the holes and slide the control box to the left to lock it into place. Be sure that both tabs are
engaged.
3. Inside the control box, install the mounting screws to fasten the control box to the bracket
4. On the left side insert the heater power cord through the access hole and connect the black wire to H-1, the white
power wire to H-2 of the TB-1 terminal and the green ground wire from the heater to the heater ground terminal (just
below and center of TB-1 terminal block).
5. On the top right side of the control box, connect the two thermistors and the pressure switch input.
6. On the right side, connect the ribbon cable for the main panel and the cord for the auxiliary panel, if applicable.
7. Along the bottom of the control box, connect all components back to original ag terminals.
Wiring the Line Voltage Conduit to Terminal Block TB-1
CAUTION
If the line voltage is wired incorrectly, damage to the control box may occur.
ELECTRICAL REQUIREMENTS
ALL SPAS MUST BE WIRED IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL
CODES. ALL ELECTRICAL WORK SHOULD BE DONE BY AN EXPERIENCED, LICENSED ELECTRICIAN. WE
RECOMMEND THE USE OF APPROPRIATE ELECTRICAL CONDUIT, FITTINGS, AND WIRE FOR ALL CIRCUITS.
1. The wiring instructions are located below.
2. Refer to the illustrations at the bottom of the page and locate the spa model and operating voltage.
3. Wire the terminal block (TB-1) as shown: Figures 1 - 3
Input Wiring
1. Connect the Blue (Hot) wire from the sub panel 20 amp breaker terminal L1 to TB-1, terminal 2.
2. Connect the Red (Hot) wire from the sub panel 20 amp breaker terminal L2 to TB-1, terminal 4.
3. Connect the Blue (Hot) wire from the sub panel 30 amp breaker terminal L1 to TB-1, terminal 5.
4. Connect the Red (Hot) wire from the sub panel 30 amp breaker terminal L2 to TB-1, terminal 6.
5. Connect the White (Neutral) wire from the sub panel 30 amp breaker terminal N to TB-1, terminal 7.
6. Connect the Green (Ground) wire from the sub panel ground bar to the source grounding lug.
7. CANTABRIA ONLY - Verify power jumpers (A) are set across terminals 1-2 and 3-4 on TB-1 Figure 2.
Figure 1 Figure 2
CANTABRIA
GENEVA • NIAGARA • TAHITIAN • SALINA
KAUAI • MARTINIQUE • MAKENA
A
A
Page 2