Trouble-Shooting Error Symptoms Section 5 Maintenance and Trouble-Shooting
454 3BSE035980-511
A Too many instances in application
message appears.
The maximum number of above 65534
instances has been reached.
1.Try to reduce your application, see Statistics for
Application on page 446.
Cannot create/open a control project. An
Action denied message appears.
License Error. When the Control Builder
connects to an 800xA system a Control
Builder license is checked out. If the
license does not exist or the license
count has been exceeded, a dialog
window appears on the screen,
displaying that the action was denied.
1.Close a running Control Builder client temporarily, in
order to release a license.
2.Contact your System Administrator to extend the
number of license features.
Cannot download to a controller without
a system wide annoyance behavior.
License Error. After the Project Explorer
has made a successful download to a
controller, the Controller Capacity Points
(CCP) information is stored and a
license enforcement cycle is started by a
license agent. If the maximum number of
CCP counts is exceeded, the license
server will start a system wide
annoyance behavior.
1.Check the CCP count of each controller (that
participated in the download) from the corresponding
Controller aspect pane (select CCP tab) for each
controller, and add the CCP counts. See Checking the
CCP Count for a Controller in System 800xA Control,
AC 800M, Getting Started (3BSE041880*) manual.
2.Contact your System Administrator to increase the
maximum number of CCP counts in the CCP license.
The MMS Server, OPC Server, Tool
Routing Service, or SoftController fails.
1.Click OK.
2.Locate the two crash dump files (see Crash Dumps for
Analysis and Fault-Localization on page 435).
3.Read the Session Log, and see if there is any
information that points to the source of the problem.
4.Make an error report and include the log file.
Table 44. Examples of error symptoms and suggested measures. (Continued)
Error Symptom Measure